1. The arrester unit can be loaded and unloaded at any time with electricity, especially suitable for places where power failure is not suitable. 2. With a disconnector, when the arrester unit fails, it can automatically fall down and exit operation to ensure the normal operation of the line. 3. When the unit falls down, a clear sign is formed, which is easy to find and repair and replace in time. 4. The arrester adopts composite jacket, and the drop mechanism adopts composite pillar, which has good water repellency and strong anti-fouling ability. a.An ambient temperature of -40 degrees to +40 degrees C b.Height is not more than 3000m c.Power frequency of 48 Hz~62Hz d.The maximum wind speed of no more than 35m/s e.Seismic intensity of 7 degree and below






1. This product should be installed on the line of the system and equipment whose rated voltage is consistent with the rated voltage of the arrester. 2. Before installation and use, please check the tightness between the arrester element and the drop mechanism to ensure good contact and flexible casting. 3. Adjustment method: Rotate the copper contact (with pull ring) on the arrester to make the opening pulling force within 6~10KG, and keep the pull ring side of the copper contact facing outward, and then tighten the lower nut to make the pull ring difficult turn. 4. When installing, the arrester should be at an angle of 15~30 degrees with the vertical line, and the distance between them should not be less than 200mm.